4.3 Switching Functions
The two switching functions can be adjusted to any pressure
within the whole measurement range ( 13).
The current setpoint setting
is output at the D-Sub connector instead of the measurement
signal ( 18) and can be measured with a voltmeter after
the <SP> button is pressed, or
can be read/written via the RS232C interface.
If the pressure is lower than the setpoint, the corresponding LED
is lit (<1> or <2>) and the corresponding relay ( 18) is
energized.
Measurement signal (Pressure p)
Time t
M
e
a
s
u
r
e
m
e
n
t
v
a
l
u
e
Off
On
Hysteresis
(1% F.S.)
Off
Threshold value
Setpoint